Damper Motor Orange Cover Conversion

Damper Motor Orange Cover Conversion
Damper Motor Orange Cover Conversion
Damper Motor Orange Cover Conversion Specifications: Fail-Safe Non-Spring ... Read More

  • Stock: On Order
  • Brand: 1246
  • Type: 12-54-219

Available Options

Damper Motor Orange Cover Conversion

Specifications:

Fail-Safe Non-Spring
Torque 45 in-lbs [5 Nm] mininum
Control Input 2-10 VDC
Input Impedance 100k _ for 2 to 10 VDC (0.1 mA), 500 Ω for 4 to 20 mA
Position Feedback 2-10 VDC Feedback
Running Time (motor) 95 seconds constant, independent of load
Running Time (fail-safe) --
Power Supply 24VAC ± 20%, 50/60 Hz, 24VDC ±10%
Power Consumption running: 1.5 W, holding: 0.4 W
Transformer Sizing 3.0 VA (class 2 power source)
Electrical Connection 3 ft, 18 GA plenum rated cable with 1/2" conduit connector
Overload Protection electronic thoughout 0 to 95° rotation
Shaft Diameter Standard: 1/4" to 5/8" round, centers on 5/8", 3/4" clamp available
Angle of Rotation max. 95°, adjustable with mechanical stop
Direction of Rotation (motor) Reversible with switch
Direction of Rotation (fail-safe) --
Position Indication reflective visual indicator (snap on)
Manual Override external push button
Humidity 5 to 95% RH non condensing (EN 60730-1)
Ambient Temperature -22°F to 122°F [-30°C to 50°C]
Ambient Temperature (safety) --
Storage Temperature -40°F to 176°F [-40°C to 80°C]
Noise Level max 35 db (A)
Housing Material UL94-5VA
Housing NEMA 2, IP54, UL enclosure type 2; NEMA 1, IP20 -T
Agency Listing cULus acc. to UL60730-1A/-2-14, CAN/CSA E60730-1:02, CE acc. to 2004/108/EEC and 2006/95/EC
Quality Standards ISO 9001
Weight 1.1 lbs (0.50 kg)
Vortron Smokehouse Damper Motor Exhaust control 0-100% Positioner for surface mounting, suitable for modulating servomotors LM..A-SR, NM..A-SR, SM...